| Model |
AS-HC50K-114KWH |
| Battery Parameters |
| Battery Chemistry |
LiFePO4 |
| Total Capacity |
114KWH |
| Nominal Capacity |
280AH |
| Nominal Voltage |
409.6V |
| Operating Voltage Range |
358.4V-460.8V |
| Max Charging Current |
168A |
| Max Discharge Current |
70A |
| Storage Temperature Range |
‘-10℃-45℃ |
| Charging temperature range |
0℃-55℃ |
| Discharging temperature range |
‘-20℃-55℃ |
| Operating RH |
10%-90% |
| Storage and Transportation RH |
5%-85% |
| Working Altitude |
≤3000m |
| Communication Type |
CAN/RS485 |
| Dimension |
1058(W)*845(D)*1386(H)mm |
| Net Weight |
≈1200kg |
| Cooling Mode |
Air Cooling |
| |
|
| PCS Parameters |
| Battery side parameters |
| Maximum cell voltage |
850V |
| Rated battery range |
200V |
| Rated battery voltage range |
320-820V |
| Maximum cell current |
150A |
| Pv parameter |
| Maximum power |
38.4KW+38.4KW |
| Maximum PV voltage |
850V |
| Pv starting voltage |
250V |
| MPPT voltage range |
200-800V |
| Maximum PV current |
64A+64A |
| AC side (grid connection) |
| Rated power |
50KVA |
| Rated current |
87A |
| Rated grid voltage |
400V/230V |
| Grid voltage range |
-20%~15% |
| Starting inrush current |
8.5A |
| Grid frequency range |
50Hz (47Hz-52Hz) or 60Hz (57Hz-62Hz) |
| Current harmonics |
<3% |
| Power factor |
’-1~1 |
| AC side (off-grid) |
| Rated output power |
50KVA |
| Maximum output power |
55KVA |
| Maximum output current |
80A |
| Rated voltage |
400V/230V |
| Output voltage harmonics |
<3% |
| Imbalance degree |
100% |
| Output overload |
1.1 x long term/1.25 x 100S/1.5 x 100ms |
| System parameters |
| And off-grid switching time |
< 10ms |
| Maximum efficiency |
97.80% |
| Power consumption |
Standby < 20W/No load < 100W |
| Level of protection |
IP20 (core control section IP5X) |
| Dimensions |
440 * 670 * 200mm |
| Weight |
45kg |
| Temperature range |
-25 ~ 60 ℃ (for derating greater than 45 ℃) |
| Humidity |
5~95% |
| Cooling method |
Intelligent forced air cooling |
| Altitude |
4000m (for derating over 2000m) |